Permit Number: T13CM02494
Parcel: 117160100

Address:
1 E TOOLE AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T13CM02494
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change provide informtion showing 700 pound loads for A/C units will be acceptable on the roof.
05/07/2013 KEN BROUILLETTE FIRE REVIEW Approved
05/07/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
05/07/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02494
1 E Toole AV

1. The Panel shows a 120/208v ( should also be rated for 120/240v) system with Phase C as high leg. NEC 2011,408.3, the higher voltage leg shall be
Phase B. Since this panel is being upgraded, has to be brought to current code.
2. The #12 conductors being tapped from the 300MCM AL
conform with the 10' tap rule of 2011 NEC 240..21.B. with 25a divided by 200a fuse at Main disconnect being over the 10% required, however the # 12 conductors must end being protected by an overcurrent device per it's ampacity.
3. Describe the method to be used at junction boxes on the roof used to splice the 300MCM AL, #6 CU and the #12 CU conductors.
4. 2011 NEC requires ampacity adjustments for raceways
exposed to Sunlight on roofs per 310.15.B.3.C. Show how installation complies. Distance off roof on conduit to be
factor.

Ray Majuta
Elect Plan Review
PDSD, C of Tucson
5/7/2013
05/07/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed