Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02467
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations; the minimum Zp value was used instead of the maximum Zp value. [Initial comment: Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.] |