Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02467
Parcel: 11706320C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM02467
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations; the minimum Zp value was used instead of the maximum Zp value. [Initial comment: Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.]