Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02467
Parcel: 11706320C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02467
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/02/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the water heater platform and show how the proposed platform is to be connected to the building structure. Reference: Section 301.2, IPC 2012.
2. Clarify the design of the propane supply to the air handler. Provide the initial and secondary supply pressures to be used. Reference: Sections 402.4 and 402.5, IFGC 2012.
3. Verify the discharge size for the pressure relief valve for the water booster pump. Reference: Section 606.5.10, IPC 2012.
05/06/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the airflow from AHU-1 is to be distributed among the three major building areas (i.e. CFM/room).
2. Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.
3. Provide justification for the use of a Zone Air Distribution Effectiveness (Ev) of 1.0 for a ceiling supply, ceiling return system using a gas-fired heating section. Reference: Section 403.3.1.2, IMC 2012.
4. The Mechanical Compliance Certificate indicates that a credit has been taken for using MERV 9-12 filtration but the specifications call for MERV 8 filtration; adjust the filter specification or recalculate the pressure drop adjustment. Reference: Section C403.2.10 and Table C403.2.10.1 (2), IECC 2012.
05/07/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET SP-1
1. Under the CODE REVIEW: Delete all reference to ADAAG and correct ANSI to 2009 Edition, ICC A117.1.
2. Correct Occupancy Load to 273.
SHET A1.2
3. At detail 1-A, provide 3'-0" wide urinal stall.
4. At Floor Plan:
a. Provide 3'-0" wide urinal stall.
b. Provide a minimum 42" wide corridor access to the accessible stall.
STRUCTURAL DRAWINGS
5. Provide structural calculations for:
a. All structural details and framing design shown on sheets S1.1 through S3.3.
b. Water heater and water pressure booster platforms.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2013 CPIERCE1 APPROVAL SHELF Completed
05/07/2013 CPIERCE1 REJECT SHELF Completed