Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02426
Parcel: 124050520

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02426
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2013 MARTIN BROWN FIRE REVIEW Approved
05/06/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G-001; SITE AND OCCUPANCY: THE ACCESSIBILITY CODE ENFORCED BY THE CITY OF TUCSON IS THE ICC/ANSI A117.1-2009. REVISE.
2. SHEET A-501; WALL TYPES: MOVE THIS SCHEDULE TO SHEET A-120.
3. SHEET A-502; DETAIL 1: PROVIDE THE CONNECTION OF THE VERTICAL STUDS TO THE EXISTING STRUCTURE ON THIS DETAIL.
4. SHEET A-502; DETAIL 1: PROVIDE THE CONNECTION OF ALL METAL STUDS INDICATED ON THIS DETAIL.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. NO SUBSEQUENT REVIEWS WILL BE PERFORMED UNTIL RESPONSES ARE PROVIDED.
05/13/2013 ROBERT SHERRY WATER REVIEW Approved
05/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing plans for the new work by including water isometrics and waste and vent isometrics showing the relationship of the new work to the existing plumbing. Reference: Section 107.2.1, IBC 2012.
2. Sheet A110 shows what appear to be existing tank-type water closets but flush valve water closets are to replace the existing water closets. Table 604.3, IPC 2012 requires a design capacity of 25 GPM for supply pipes serving siphonic flush-valve water closets. If tank-type water closets are being replaced by flush-valve water closets, verify that the water velocity in the existing supply pipes will not exceed the maximum velocity recommended by the piping manufacturer or accepted engineering practice (e.g. 8 FPS in copper tubing). Reference: Sections 303.2 and 604.1, IPC 2012.
3. Verify that the relief ports for the specified backflow preventers (Zurn 740) are directed to an approved indirect waste receptor so that water leakage will not cause damage. Reference: Section 608.14, IPC 2012.
4. Show how the 3-compartment sink is to be installed. Reference: Sections 801.2 and 802.1.8, IPC 2012.
05/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2013 CPIERCE1 REJECT SHELF Completed