Permit Number: T13CM02392
Parcel: 110113610

Address:
2480 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM02392
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The detail has been revised to show an air gap but the three compartments still share a common indirect waste drain. [Initial comment: Revise all of the drains for the two 3-compartment sinks, PL3C-18 and PL3C-20, (detail PSD-7/P5.2) to be independently routed to an indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2013 CPIERCE1 APPROVAL SHELF Completed
06/19/2013 CPIERCE1 OUT TO CUSTOMER Completed