Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02392
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The detail has been revised to show an air gap but the three compartments still share a common indirect waste drain. [Initial comment: Revise all of the drains for the two 3-compartment sinks, PL3C-18 and PL3C-20, (detail PSD-7/P5.2) to be independently routed to an indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2013 | CPIERCE1 | APPROVAL SHELF | Completed |
| 06/19/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |