Permit Number: T13CM02392
Parcel: 110113610

Address:
2480 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02392
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2013 MARTIN BROWN FIRE REVIEW Approved
05/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G0.1; PROJECT CODES: THE IBC, IEBC, IMG, IECC, IFGC, IPC, AND IFC ARE ALL CURRENTLY USING THE 2012 EDITION, WHILE THE NEC IS USING THE 2011 EDITION. ADD THE ICC/ANSI A 117.1-2009 ACCESSIBILITY CODE.
2. SHEET A1.1; WALL LEGEND: PROVIDE THE NEW 4" WALL METAL STUD GAUGE AND SPACING.
3. SHEET A1.1; WALL LEGEND: PROVIDE THE NEW 5" WALL METAL STUD GAUGE AND SPACING. IS 5" CORRECT? VERIFY.
4. SHEET A1.2; DEMOLITION PLAN LEGEND: THIS IS NOT A DEMOLITION PLAN. REVISE THE TITLE.
5. SHEET A4.1; DETAIL 11: A NOTE INDICATES STEEL STUDS PER SCHEDULE. WHERE IS THE SCHEDULE? PROVIDE.
6. SHEET A4.2; MOUNTING HEIGHT SCHEDULE: ADD THE TOILET PAPER DISPENSER LOCATION PER THE ICC/ANSI FIGURE 604.9.2.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. NO SUBSEQUENT REVIEWS WILL BE PERFORMED WITHOUT RESPONSES.
05/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise all of the drains for the two 3-compartment sinks, PL3C-18 and PL3C-20, (detail PSD-7/P5.2) to be independently routed to an indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.
2. Plumbing schematic B/P6.1 shows two new horizontal vents below the floor; this is not allowed under the 2012 IPC. Reference: Section 905.4, IPC 2012.
05/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2013 CPIERCE1 REJECT SHELF Completed