Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02339
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
04/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/19/2013 ROBERT SHERRY WATER REVIEW Approved
04/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.1; FLOOR PLAN: THE WATER FOUNTAIN IS REQUIRED TO BE A HIGH/LOW OR SINGLE POINT OF USE DISPENSER. PROVIDE.
2. SHEET A3.1; WALL TYPES: INTERIOR PARTITIONS MUST MEET THE REQUIREMENTS OF IBC SECTION 1607.14 FOR A 5 PSF HORIZONTAL LOADING. PROVIDE A BRACING DETAIL ON THE DRAWINGS, INCLUDING BRACING SIZE AND SPACING, AND THE CONNECTION SIZE AND QUANTITY AT THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
04/19/2013 JASON GREEN ENGINEERING REVIEW Approved
04/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/19/2013 MARTIN BROWN FIRE REVIEW Approved
04/19/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/24/2013 SPOWELL1 WWM REVIEW Passed