Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02311
Parcel: 12810082B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM02311
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Boilers are required to comply with the rules contained in Article 4 (Arizona Boilers and Lined Hot Water Heaters) of the Arizona Administrative Code. http://www.azsos.gov/public_services/Title_20/20-05.htm#ARTICLE_4
2. Provide equipment data for the water heaters, the steam generator, and the air vacuum. Reference: Section 107.2.1, IBC 2012.
3. Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply and sanitary waste systems to become locally overloaded (e.g. "Connect the new sanitary sewer to the existing sanitary sewer of equal or greater size."). Reference: Section 107.2.1, IBC 2012.
4. Show the sizes, routes, and terminations for the steam and air vacuum piping. Reference: Section 107.2.1, IBC 2012.
5. Provide a design for the mounting shelf for the water heater. Reference: Section 301.2, IPC 2012.
6. Install the proposed vacuum relief valve for the water heaters per the manufacturer's listing information, i.e. on the cold water supply to the water heater. Reference: Section 303.2, IPC 2012.
7. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
8. Clarify the pipe sizes for the water distribution and coordinate the plumbing plans, the water isometrics, and the water heater detail (e.g. the cold water line from the water heater to the two restrooms is shown as being ½", ¾", and 1"). Reference: Section 107.2.1, IBC 2012 and Section 604.1, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2013 SHANAE POWELL OUT TO CUSTOMER Completed
05/07/2013 CPIERCE1 REJECT SHELF Completed