Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02311
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/18/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
04/19/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/19/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/22/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the control specifications so that each rooftop unit has a thermostatic control that provides for automatic shutdown and start-up control. Reference: Section C403.2.4, IECC 2012. |
04/22/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02311 1. Provide a fault current calculation for Panels A and B. 2. The feeder from Landlords service to Panel (2 sets of 4-#500 kcm) is equal to 760 amps per the 75 degree column in Table 310.15.B. The terminations in Panel A is questionable for these sized conductors. Is this correct ? Ray Majuta Elect Plan Review DSD, Tucson 4/22/2013 Ray@tucsonaz.gov |
04/22/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/22/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
04/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
04/24/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |