Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02311
Parcel: 12810082B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02311
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
04/18/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
04/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the control specifications so that each rooftop unit has a thermostatic control that provides for automatic shutdown and start-up control. Reference: Section C403.2.4, IECC 2012.
04/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02311

1. Provide a fault current calculation for Panels A and B.
2. The feeder from Landlords service to Panel (2 sets of 4-#500 kcm) is equal to 760 amps per the 75 degree column in Table 310.15.B. The terminations in Panel A is questionable for these sized conductors. Is this correct ?

Ray Majuta
Elect Plan Review
DSD, Tucson
4/22/2013
Ray@tucsonaz.gov
04/22/2013 ROBERT SHERRY WATER REVIEW Approved
04/22/2013 KEN BROUILLETTE FIRE REVIEW Approved
04/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/24/2013 CPIERCE1 WWM REVIEW Needs Review