Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02292
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/14/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
05/14/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/14/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The revised natural gas piping plans now indicate that an existing ¾" line runs from the meter manifold up to the second floor ceiling space. Where is the pressure regulator for this line and is it serving furnace F-1? [Initial comment: Clarify the natural gas distribution system. The existing gas meter is shown as having a 2" low pressure gas pipe and a ¾" medium pressure gas pipe connected to it. An additional 1-1/4" low pressure gas pipe is shown rising to the roof but its origin is not clear. Where is the regulator for the 2" low pressure gas pipe located? Also, to what meter are the water heaters and furnace F-1 connected?] |
05/14/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |