Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM02292
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02292
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2013 STEVE SHIELDS ZONING REVIEW Approved
04/18/2013 KEN BROUILLETTE FIRE REVIEW Denied BASEMENT IS REQUIRED TO HAVE FIRE SPRINKLER PROTECTION-PLANS SHALL INDICATE THE ADDITION OF FIRE SPRINKLERS IN THIS AREA PRIOR TO FINAL OF PERMIT T13CM02292
PLEASE SHOW EXISTING BASEMENT ON FLOOR PLANS
PLEASE INDICATE THAT THE 2012 IFC IS THE APPLICABLE FIRE CODE FOR THIS PROJECT WITH LOCAL MODIFICATIONS.
PLEASE INDICATE THAT A FIRE ALARM SYSTEM IS ALSO EXISTING
04/26/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.1; PLUMBING FIXTURES: LINE TWO INDICATES 60 FEMALE RESIDENTS. INDICATE ON THIS SHEET HOW THE OCCUPANT LOAD WAS DETERMINED.
2. SHEET A2.1; ELEVATION 10: THE RESTROOM PLAN INDICATES SEVERAL LOCATIONS FOR ELEVATION 10/A2-1. VERIFY.
3. SHEET A2.1; RESTROOM PLAN: A DETAIL REFERENCE ON THE SOUTH RESTROOM WALL INDICATES 1/A3.1. REVISE REFERENCE.
4. SHEET A2.1; REFLECTED CEILING PLAN: AN ELEVATION INDICATOR IN THE MAKEUP ROOM REFERENCES ELEVATIONS 1, 2, 3, AND 4 ON SHEET A2. REVISE REFERENCES.
5. SHEET A4.1; INTERIOR PARTITIONS: THE IBC SECTION 1607.14 REQUIRES INTERIOR PARTITIONS OVER 6' IN HEIGHT TO HAVE ADEQUATE STRENGTH TO RESIST A HORIZONTAL LOAD OF 5 PSF. PROVIDE BRACING AT THE TOP OF THE PARTITIONS THAT EXTENDS TO THE STRUCTURE ABOVE. INDICATE ON A DETAIL THE BRACING SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION, AND CONNECTION TO THE STRUCTURE ABOVE.
6. GENERAL: PROVIDE A SITE PLAN IN THE DRAWINGS PER THE IBC SECTION 170.2.5.
7. GENERAL: PROVIDE WALL ELEVATIONS, INCLUDING GRAB BARS AND SHOWER CONTROL LOCATIONS, PER THE ICC/ANSI SECTION 608, FOR THE ACCESSIBLE SHOWER STALL.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. SUBSEQUENT REVIEWS WILL NOT BE PERFORMED UNTIL RESPONSES ARE RECEIVED.
05/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the restroom exhaust fans (EF-1 and EF-2) are controlled; the exhaust schedule calls for the fans to have a separate switch with the lights and to be interlocked per the electrical division specifications while the electrical plans call for the use of a time switch. Reference: Section 107.2.1, IBC 2012.
2. Provide justification for the use of a Zone Air Distribution Effectiveness (Ev) factor of 1.0 for a ceiling supply, ceiling return system using a gas-fired furnace. Reference: Section 403.3.1.2, IMC 2012.
3. The schedule for the gas-fired rooftop units calls out remark #7 for all of the units; provide remark #7.
05/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the natural gas distribution system. The existing gas meter is shown as having a 2" low pressure gas pipe and a ¾" medium pressure gas pipe connected to it. An additional 1-1/4" low pressure gas pipe is shown rising to the roof but its origin is not clear. Where is the regulator for the 2" low pressure gas pipe located? Also, to what meter are the water heaters and furnace F-1 connected?
2. Two existing water heaters are located in the basement. What is the termination point for the temperature and pressure relief valves?
3. Revise the venting method for the floor drains in room 237. All vents located within a building shall rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
4. The specified temperature mixing valve (Watts N170-M2) is more properly referred to as a "hot water extender mixing valve" and is an obsolete product for which Watts has not identified a replacement product. Revise the design to comply with the requirements of Section 607, IPC 2012 with regard to approved temperature control valves.
05/01/2013 ROBERT SHERRY WATER REVIEW Approved
05/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved