Permit Number: T13CM02183
Parcel: 117170590

Address:
222 S 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM02183
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2013 MARTIN BROWN FIRE REVIEW Approved
04/19/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: LA Fitness Expanson
T13CM02183
Structural Plan (1st Review)

TRANSMITTAL DATE: April 19, 2013

1. The structural plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the structural plans sshieuntil a development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/07/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please have the structural engineer that completed the structural calculations seal and sign the structural details shown on the documents.
2. Please change the accessible code requirements to the 2010 ADASAD as this is a City of Tucson owned and operated property.
SHEET A1
3. At detail 1A1, change the section reference to A/A2.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2013 CPIERCE1 OUT TO CUSTOMER Completed