Permit Number: T13CM02164
Parcel: 13629003F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM02164
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. THE STRUCTURAL CALCULATIONS DESIGN OF THE PURLINS DOES NOT AGREE WITH THE DETAIL 01 ON SHEET S2. CLARIFY.
2. THE STRUCTURAL CALCULATIONS DESIGN OF THE BEAMS DOES NOT AGREE WITH THE DETAIL 07 ON SHEET S2. CLARIFY.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed