Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T13CM02164
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. THE STRUCTURAL CALCULATIONS DESIGN OF THE PURLINS DOES NOT AGREE WITH THE DETAIL 01 ON SHEET S2. CLARIFY. 2. THE STRUCTURAL CALCULATIONS DESIGN OF THE BEAMS DOES NOT AGREE WITH THE DETAIL 07 ON SHEET S2. CLARIFY. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/06/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |