09/11/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 9-11-13
Activity: T13CM02150
Address: 1651 E. Lind Rd #1
Applicant: Rick McLain

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Specify the length and demand of the proposed gas line, G2413.1, Table G2413.4 (1).
2. Show location and sizes of all plumbing vents, P3101.1.

ELECTRICAL PLAN:
3. Show the location of the subpanel C with a 30"W x 36"D clear working space, E3405.2, E3405.4.
4. All outlets specified in section E3902.12 shall be protected with combination-type arc-fault breakers (not just bedroom outlets).
5. Provide carbon monoxide alarms per R315. Alarms must be installed in residences with attached garages and/or fuel-fired appliances when any work is performed that requires a permit.
6. Specify faceplate grounding per E4001.11.1.
7. Specify tamper resistant receptacles per E4002.14.
8. Show locations of smoke detectors in hallway leading to sleeping rooms. All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R314.

OUTDOOR LIGHTING CODE
9. Include unshielded flood light on outdoor lighting calculation, OLC 3.1.2.