Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T13CM02142
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2013 | CPIERCE1 | APPROVAL SHELF | Completed |
| 08/28/2013 | CPIERCE1 | OUT TO CUSTOMER | Passed |