Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM02142
Parcel: 11904600L

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T13CM02142
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2013 CPIERCE1 APPROVAL SHELF Completed
08/28/2013 CPIERCE1 OUT TO CUSTOMER Passed