Permit Number: T13CM02142
Parcel: 11904600L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02142
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/11/2013 LOREN MAKUS ENGINEERING REVIEW Approved
04/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a mechanical energy code compliance certificate.
2. Provide an automatic start capabiliy for the HVAC controls. Reference: section C403.2.4.3.3, IECC 2012.
3. Provide ventilation calculations using the 2012 IMC.
4. Clarify the status of the A/C units with regard to economizers. The M1.1 appears to show economizers but the schedule does not include any economizers.
5. Clarify the type of A/C units being installed; the schedule on M3.1 and the keynotes on M1.1 indicate heat pumps but the plumbing drawings show that they will be served with gas.
04/12/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
04/12/2013 ROBERT SHERRY WATER REVIEW Approved
04/12/2013 STEVE SHIELDS ZONING REVIEW Approved
04/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/12/2013 MARTIN BROWN FIRE REVIEW Approved
04/18/2013 CPIERCE1 WWM REVIEW Passed