Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/11/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/11/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical energy code compliance certificate. 2. Provide an automatic start capabiliy for the HVAC controls. Reference: section C403.2.4.3.3, IECC 2012. 3. Provide ventilation calculations using the 2012 IMC. 4. Clarify the status of the A/C units with regard to economizers. The M1.1 appears to show economizers but the schedule does not include any economizers. 5. Clarify the type of A/C units being installed; the schedule on M3.1 and the keynotes on M1.1 indicate heat pumps but the plumbing drawings show that they will be served with gas. |
04/12/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/12/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/12/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/12/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/18/2013 | CPIERCE1 | WWM | REVIEW | Passed |