Permit Number: T13CM02138
Parcel: 12417096A

Address:
909 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM02138
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2013 JASON GREEN ENGINEERING REVIEW Approved
04/15/2013 KEN BROUILLETTE FIRE REVIEW Approved
04/22/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET S1.2
1. Please provide certification of special inspectors as indicated.
SHEET S2.1
2. The steel pipe bridge indicates B2 to be C12 x 20.7 while calculations call for a W12 x 22. Please reconcile.
3. An over the counter correction approval is available.
END OF REVIEW
04/23/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/26/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/26/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the civil site plan (referenced on sheet P1.0) that shows the extension of the building sewer to the public sewer. Reference: Section 107.2.1, IBC 2012.
2. Provide a full-open valve for the water service at the equipment building entrance. Reference: Section 606.1(2), IPC 2012.
3. Show how contamination of the water distribution system due to connections to process equipment is prevented. Reference: Section 608.1, IPC 2012.
4. Clarify the installation of the two floor sinks located in the equipment room. The plumbing schedule on sheet P2.0 calls out a 1-1/2" vent and a trap primer for each floor sink but these are not shown with either fixture. Reference: Section 107.2.1, IBC 2012 and Sections 901.2.1 and 1002.4, IPC 2012.
04/26/2013 ROBERT SHERRY WATER REVIEW Denied Provide the civil site plan (referenced on sheet P1.0) that shows the location of the new ¾" water meter and the existing 1" RPBP. Reference: Section 107.2.1, IBC 2012.
04/30/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2013 SHANAE POWELL OUT TO CUSTOMER Completed
05/22/2013 CPIERCE1 REJECT SHELF Completed