Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T13CM02112
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2013 | MICHAEL ST. PAUL | PLANNING-CITY HALL | REVIEW | Approved | |
| 04/12/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | Add note regarding conformance to 2012 International Fire Code. I think building has hose valve(s) on roof. Confirm location,access, show on plans. Need quantities hazardous materials (gallons of electrolyte in batteries. Confirm under maximum allowable quantities from the fire code. |
| 04/15/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/22/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/25/2013 | GREGORY MCNEAL | COMMUNICATIONS | REVIEW | Approved | |
| 04/25/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 08/08/2013 | CPIERCE1 | REJECT SHELF | Completed |