Permit Number: T13CM02055
Parcel: 137055240

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02055
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm02055

1. Last review asked for circuits to be assigned and a current panel schedule, circuits 41,38,40 used in power plan have not been added to panel, the spaces and loads are empty.

Ray Majuta
Electrical Plan Review
5/10/2013
520-837/4988