Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM02055
Parcel: 137055240

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02055
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2013 STEVE SHIELDS ZONING REVIEW Approved
04/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02055
1189 W Irvington
Famous Footwear

Per City of Tucson Commercial Submittal Requirements:
1. Assign circuits to each receptacle,light,appliance and indicate Panel circuit assigned to.
2. Provide a panel schedule, showing location, voltage & amperage & phase description, show loads.
3. Show where panel gets fed from, existing load on service plus this space load for new total.
4. No Emergency or exit lighting provided.


Please review City of Tucson Commercial Submittal Requirements , may be obtained on City's Web page under Departments to Building Codes, to Commercial Submittal Requirements.

Ray T Majuta
Electrical Plan Review
DSD, Tucson
4/9/2013
Ray.Majuta@tucsonaz.gov
04/09/2013 ROBERT SHERRY WATER REVIEW Approved
04/09/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0; CONSTRUCTION KEYNOTES: NOTE 3 WAS NOT FOUND ON THE PLAN. VERIFY
2. SHEET A2.0; CONSTRUCTION KEYNOTES: NOTE 5 INDICATES NOT USED, BUT IT IS SHOWN ON THE PLAN (EAST WALL). CLARIFY.
04/09/2013 JASON GREEN ENGINEERING REVIEW Approved
04/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/09/2013 MARTIN BROWN FIRE REVIEW Approved
04/09/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/10/2013 FRODRIG2 WWM REVIEW Passed