Permit Number: T13CM02050
Parcel: 136061580

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02050
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2013 STEVE SHIELDS ZONING REVIEW Approved
04/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a return grille in the massage room. Reference: Tucson Code, Chapter 7, Article VVII, Section 7-137.
2. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
04/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied
04/09/2013 ROBERT SHERRY WATER REVIEW Approved
04/09/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2013 JASON GREEN ENGINEERING REVIEW Approved
04/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012.
2. Provide material standards for all plumbing fixtures, including those being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
3. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
04/09/2013 MARTIN BROWN FIRE REVIEW Approved
04/09/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/24/2013 SPOWELL1 WWM REVIEW Needs Review