Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02050
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/09/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/09/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a return grille in the massage room. Reference: Tucson Code, Chapter 7, Article VVII, Section 7-137. 2. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. |
04/09/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
04/09/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/09/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/09/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
04/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. 2. Provide material standards for all plumbing fixtures, including those being provided by others. Reference: Sections 303.4 and 402, IPC 2012. 3. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. |
04/09/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/09/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/24/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |