Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01990
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide independent indirect waste lines. [Initial comment: Revise the drains for the new 3-compartment sink (detail PSD-7/P5.1) located near column D-8 to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/12/2013 | CPIERCE1 | REJECT SHELF | Completed |