Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE COMMENTS FROM FIRST DENIAL DATED 4-5-13
04/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the drains for the new 3-compartment sink (detail PSD-7/P5.1) located near column D-8 to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.
2. Verify that the tempered water for the lavatories is provided by thermostatic mixing valves conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
04/30/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2013 SHANAE POWELL OUT TO CUSTOMER Completed
05/02/2013 CPIERCE1 REJECT SHELF Completed