Review Details: COMMERCIAL - TI
Permit Number - T13CM01990
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE COMMENTS FROM FIRST DENIAL DATED 4-5-13 |
| 04/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the drains for the new 3-compartment sink (detail PSD-7/P5.1) located near column D-8 to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012. 2. Verify that the tempered water for the lavatories is provided by thermostatic mixing valves conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 04/30/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/02/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 05/02/2013 | CPIERCE1 | REJECT SHELF | Completed |