Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T13CM01952
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations from the 2006 IMC to the 2012 IMC. Supply sufficient outside air to provide makeup air for the restroom exhaust. |
| 04/04/2013 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 04/04/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/04/2013 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 04/04/2013 | ANY | WWM | REVIEW | Active | |
| 04/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a drinking fountain or a point-of use water dispenser. |
| 04/04/2013 | ANY | ENGINEERING | REVIEW | Active | |
| 04/04/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Need additional information: 1. F-2 Occupancy is noted-what are they manufacturing? 2. If they are storing and the Occupancy classification needs to be changed to a type S, then please indicate the type of storage and height. Any existing information on the fire sprinkler system, such as Densist would be helpful. It is possible the warehouse area needs to meet High Piled Storage provisions of the IFC. |
| 04/04/2013 | ANY | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active |