Permit Number: T13CM01952
Parcel: 10703141D

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T13CM01952
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
04/04/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations from the 2006 IMC to the 2012 IMC. Supply sufficient outside air to provide makeup air for the restroom exhaust.
04/04/2013 ANY ELECTRICAL-COMMERCIAL REVIEW Active
04/04/2013 ROBERT SHERRY WATER REVIEW Approved
04/04/2013 ANY BUILDING-COMMERCIAL REVIEW Active
04/04/2013 ANY WWM REVIEW Active
04/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a drinking fountain or a point-of use water dispenser.
04/04/2013 ANY ENGINEERING REVIEW Active
04/04/2013 KEN BROUILLETTE FIRE REVIEW Denied Need additional information:
1. F-2 Occupancy is noted-what are they manufacturing?
2. If they are storing and the Occupancy classification needs to be changed to a type S, then please indicate the type of storage and height. Any existing information on the fire sprinkler system, such as Densist would be helpful. It is possible the warehouse area needs to meet High Piled Storage provisions of the IFC.
04/04/2013 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active