05/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1
1. At note 2, delete reference to ADA and insert 2009 ICC A117.1, Section 604.
2. Please provide a large scale toilet floor plan and all interior elevations showing all accessibility requirements such as dimensions, clearances, wall finishes, accessories, fixtures and signage as required by the 2012 IBC, Chapter 11 and the 2009 ICC A117.1.
END OF REVIEW