Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM01912
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/03/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T13CM01912 9044 S Houghton Site Lighting 1. The Outdoor Lighting Ordinance being used is from 2005. The table used on E6.0 (5.1) should be in the 2012 ODL Ord Table 401.1, the lumen values are also different. Option #2 has changed in allowed FC Off lumens. 2. How is the distinction made between the 3000K lamps verses the 2000k ? on cover sheet E1.0 3. The application will need to have 3 addresses, one for each Pedestal, ok to use same address with Site Lighting A-1,Site Lighting A-2 and Site Lighting A-3. Ray Majuta Elect Plan Review DSD, Tucson, 4/3/2013 Ray.Majuta@tucsonaz.gov |
| 04/04/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/04/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |