Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Original correction comment remains"CANNOT PERFORM REVIEW DUE TO LACK OF SUFFICIENT INFORMATION."

Please excuse my lack of understanding these plans, but why are you showing 2 sets of 4 PV panels tied in parallel? How does this work without a neutral line tap? How did you arrive at the 30A overcurrent protection? Are you simply using the "Redflow" device as a backup energy generator? What else is connected in Panel PPC? If the Redflow is a backup generator then how is the transfer made from utility to generator power?


Correction comment #3 partial response only "PROVIDE PANEL PPC RATING TO JUSTIFY 30A BACKFED BREAKERS" You have provided the panel rating, but backfeeding 30A onto a 100A bus is not allowed by NEC 705.12

Please contact LeeRay at 520-837-4906.