Permit Number: T13CM01878
Parcel: 107150050

Address:
2745 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM01878
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/02/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/02/2013 JASON GREEN ENGINEERING REVIEW Approved
04/02/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied CANNOT PERFORM REVIEW DUE TO LACK OF SUFFICIENT INFORMATION.

PROVIDE COMPLETE 3-LINE WIRING DIAGRAM TO INCLUDE PV PANEL WIRING, CONDUIT SIZES & DERATING FACTORS

PROVIDE PANEL PPC RATING TO JUSTIFY 30A BACKFED BREAKERS.

PROVIDE TYPE AND LOCATION OF ALL SIGNAGE REQUIRED PER ARTICLE 690 OF THE 2011 NEC.

CLARIFY DISCREPANCIES IN FEEDER SCHEDULE PP E-1. ARE YOU ASKING FOR 2 SEPARATE CONDUITS AS INDICATED IN 1-LINE FOR THIS SINGLE 240 V RUN? PLEASE DETAIL HOW YOU WOULD LIKE TO ENCASE A 3/4" X 10' COPPER ROD IN CONCRETE; VERIFY 10' Cu ROD MEETS NEC REQUIREMENTS FOR CONCRETE ENCASED ELECTRODE OR FOR GROUNDING PLATE.
04/02/2013 KEN BROUILLETTE FIRE REVIEW Approved
04/02/2013 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2013 CPIERCE1 OUT TO CUSTOMER Completed