Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM01878
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/02/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/02/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/02/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | CANNOT PERFORM REVIEW DUE TO LACK OF SUFFICIENT INFORMATION. PROVIDE COMPLETE 3-LINE WIRING DIAGRAM TO INCLUDE PV PANEL WIRING, CONDUIT SIZES & DERATING FACTORS PROVIDE PANEL PPC RATING TO JUSTIFY 30A BACKFED BREAKERS. PROVIDE TYPE AND LOCATION OF ALL SIGNAGE REQUIRED PER ARTICLE 690 OF THE 2011 NEC. CLARIFY DISCREPANCIES IN FEEDER SCHEDULE PP E-1. ARE YOU ASKING FOR 2 SEPARATE CONDUITS AS INDICATED IN 1-LINE FOR THIS SINGLE 240 V RUN? PLEASE DETAIL HOW YOU WOULD LIKE TO ENCASE A 3/4" X 10' COPPER ROD IN CONCRETE; VERIFY 10' Cu ROD MEETS NEC REQUIREMENTS FOR CONCRETE ENCASED ELECTRODE OR FOR GROUNDING PLATE. |
| 04/02/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 04/02/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |