Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01852
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE UPDATE DRAWINGS SO THEY ARE DESIGNED TO THE 2012 INTERNATIONAL CODES. THE OCCUPANCY CLASSIFICATION SHOULD BE UPDATED TOO. |
| 04/15/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Pleae provide a Site Plan. SHEET G0.1 2. All the building codes listed are incorrect. Reference the Planning and Decvelopments Services web site for a list of the most current building codes adopted by the City of Tucson. 3. The occupancy group is not B-2, it is "M" for mercantile. Please correct. END OF REVIEW |
| 04/15/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/15/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the drains for the new 3-compartment sink (detail PSD-7/P5.1) located in the produce prep area are to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012. |
| 04/15/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/25/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |