Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2013 KEN BROUILLETTE FIRE REVIEW Denied PLEASE UPDATE DRAWINGS SO THEY ARE DESIGNED TO THE 2012 INTERNATIONAL CODES.
THE OCCUPANCY CLASSIFICATION SHOULD BE UPDATED TOO.
04/15/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Pleae provide a Site Plan.
SHEET G0.1
2. All the building codes listed are incorrect. Reference the Planning and Decvelopments Services web site for a list of the most current building codes adopted by the City of Tucson.
3. The occupancy group is not B-2, it is "M" for mercantile. Please correct.
END OF REVIEW
04/15/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/15/2013 ROBERT SHERRY WATER REVIEW Approved
04/15/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the drains for the new 3-compartment sink (detail PSD-7/P5.1) located in the produce prep area are to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC 2012.
04/25/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved