Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01851
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Detail HSD-4/M6.1 shows the duct wrap for the grease duct being applied only where the duct penetrates the roof/ceiling assembly. Revise the detail to show theduct wrap extending from the duct origin to the outlet terminal. Reference: Section 506.3.11.3, IMC 2012. |
| 06/20/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |