Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01840
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/03/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/11/2013 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted ventilation calculation on sheet M3 appears to base the entire building on the ventilation rate suitable for a retail storage area. Revise the ventilation calculations using the method outlined in Section 403.3.1, IMC 2012 and identifying each occupancy type in the building. (Note that the use of rooftop units with gas-fired furnaces will result in the zone air distribution effectiveness (Ez, Table 403.3.1.2, IMC 2012) having a value of 0.8.) See also Section C403.2.5, IECC 2012 which requires the HVAC system to be able to reduce the amount of ventilation to the minimum required by Section 403.3, IMC 2012. [Initial comment: Provide calculations demonstrating that adequate ventilation is being provided, including the areas served by the variable volume control terminals. Reference: Section 403.2, IMC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/20/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/20/2013 | CPIERCE1 | REJECT SHELF | Completed |