Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01787
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/02/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The programmable thermostat described in the 2012 IECC Compliance Notes does not include a set point overlap restriction or an automatic start capability. Reference: Sections C403.2.4.2 and C403.2.4.3.3, IECC 2012. [Second comment: A programmable thermostat does not necessarily provide the features required by the 2012 IECC; indicate the features provided by the proposed programmable thermostat that comply with the code requirements.] [Initial comment: Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.4.1, C403.2.4.2, C403.2.4.3, C403.2.4.3, C403.2.4.3.1, C403.2.4.3.2, and C403.2.4.3.3, IECC 2012.] |
| 10/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The owner revision on sheet P1.1 calls for a ¾" hose bibb and a 2" indirect waste drain from the vicinity of appliance #34, a soft serve ice cream machine. Clarify the purpose of these additions. If the soft serve ice cream machine is to be water-cooled, show how the machine is to comply with the requirements of Section 929, IMC 2012, as amended by the City of Tucson. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/14/2013 | CPIERCE1 | REJECT SHELF | Completed |