Permit Number: T13CM01685
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01685
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2013 DAVID RIVERA ZONING REVIEW Approved
03/25/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/25/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01685

1. The pluming plan shows a new Electric Instant Water Heater to be installed, not in electrical plan nor panel.
2. Show location of Panel.
3. The panel does not show circuits for lighting. Provide the circuitry for lighting and loads in panel schedule in order to detremine circuit loading, due to thirty new fixtures being replaced.

Ray Majuta
Elect Plan Review
DSD, Tucson
3/24/2013
Ray.Majuta@tucsonaz.gov
03/25/2013 ROBERT SHERRY WATER REVIEW Approved
03/25/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-2: PER TABLE 2902.1 OF THE 2012 IBC, A DRINKING FOUNTAIN (HIGH/LOW) OR SINGLE POINT-OF-USE WATER DISPENSER ARE REQUIRED FOR AN OCCUPANT LOAD OF MORE THAN 15. PROVIDE.
2. SHEET A-2: PER TABLE 2902.1 OF THE 2012 IBC, A SERVICE SINK IS REQUIRED FOR AN OCCUPANT LOAD OF MORE THAN 15. PROVIDE.
03/25/2013 JASON GREEN ENGINEERING REVIEW Approved
03/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the status of the tankless water heater: new or existing?
03/25/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/25/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/27/2013 FRODRIG2 WWM REVIEW Passed