Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM01632
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM01632
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01632

Mechanical Sheet M1 has been changed to require the ex fan in the restroom to come on when RTU suppling air to area is energized. The electrical plan shows a switch energizing the fan.

Ray T Majuta
Elect Plan Review
4/11/2013
04/11/2013 RAY MAJUTA MECHANICAL-COMMERCIAL REVIEW Approved
04/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2012.
2. Show that the floor drain in the stockroom used as an indirect receptor for condensate, Water heater relief, etc, is capable of accepting the maximum discharge without splashing or flooding. Reference: Section 802.3.1, IPC 2012.
05/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved