Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01632
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM01632 Mechanical Sheet M1 has been changed to require the ex fan in the restroom to come on when RTU suppling air to area is energized. The electrical plan shows a switch energizing the fan. Ray T Majuta Elect Plan Review 4/11/2013 |
04/11/2013 | RAY MAJUTA | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/11/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2012. 2. Show that the floor drain in the stockroom used as an indirect receptor for condensate, Water heater relief, etc, is capable of accepting the maximum discharge without splashing or flooding. Reference: Section 802.3.1, IPC 2012. |
05/14/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |