Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1
1. The City of Tucson minimum lettering actual size for all construction drawings is 3/32", upper and lower case. Please revise all sheets not in compliance with this standard and resubmit.
2. Code Analysis: Delete the reference to ADA 2010. The governing accessibility code as per the 2012 IBC is Chapter 11 and the 2009 Edition of ICC A117.1. If a 2010 ADASAD accessibility review is desired, please provide an appeal to the building official for approval.
SHEET ADA1
3. Please delete this sheet in it's entirety as per accessibility requirements stated in Comment 2. If an approved appeal is provided for a 2010 ADASAD review, this sheet may remain as part of the submittal.
SHEET A2
4. As per the 2012 IBC, Section [P] 2902.3.1, toilet rooms may not be accessed through a storage room. Please reconcile.
5. Please reference where the finish and general notes are to be found.
SHEET P1
6. At detail 4, please delete all ADA references unless a building official appeal is granted.
END OF REVIEW