Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01632
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/21/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
03/21/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012. 2. Revise the termination of the condensate drain; the floor drain in the restroom cannot be used as an indirect waste receptor. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson and Section 802.3, IPC 2012. 3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated (i.e. the exhaust fan shall operate whenever air is being supplied to the restroom). Reference: Section 403.2.1 (4), IMC 2012. |
03/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/21/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/21/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
03/21/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
03/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Section 416.5, IPC 2012. 2. Indirect waste receptors shall be not be installed in bathrooms, toilet rooms, or in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Section 802.3, IPC 2012. |
03/21/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
03/21/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/27/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |