Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01592
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/20/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that adequate ventilation is to be provided. Reference: Section 403.2, IMC 2012. |
| 03/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/20/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/20/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/20/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/21/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/22/2013 | CPIERCE1 | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/22/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |