Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01588
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 2; SHEET A001; DEMOLITION PLAN: ADD DIMENSIONS AND ELEVATIONS TO THIS PLAN AS INDICATED. IF ELEVATIONS AND DIMENSIONS ARE NOT REQUIRED, REMOVE FROM THE SHEET. 2. SHEET S1; NOTES (#1): REVISE THE CODE TO THE 2012. |
| 04/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/24/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/24/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/24/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. [Initial comment: Coordinate the exhaust fan schedule (note #2) with the sequence of operation for the restroom exhaust fans as shown on sheet M301. Reference: Section 403.2.1 (4), IMC 2012.] |
| 04/25/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved |