Permit Number: T13CM01588
Parcel: 10512020C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM01588
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2; SHEET A001; DEMOLITION PLAN: ADD DIMENSIONS AND ELEVATIONS TO THIS PLAN AS INDICATED. IF ELEVATIONS AND DIMENSIONS ARE NOT REQUIRED, REMOVE FROM THE SHEET.
2. SHEET S1; NOTES (#1): REVISE THE CODE TO THE 2012.
04/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/24/2013 MARTIN BROWN FIRE REVIEW Approved
04/24/2013 ROBERT SHERRY WATER REVIEW Approved
04/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. [Initial comment: Coordinate the exhaust fan schedule (note #2) with the sequence of operation for the restroom exhaust fans as shown on sheet M301. Reference: Section 403.2.1 (4), IMC 2012.]
04/25/2013 STEVE SHIELDS ZONING REVIEW Approved