| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/06/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM01586 7801 E Kenyon DR 355.66 KW Photovoltaic System 1.Indicate on Electrical (PV) Sheets, Installation to comply with 2011 NEC. 2. Sheet PV 2.0, indicate 400 amp disconnect replacing the 200 amp disconnect to be listed and approved for installation. 3. Sheet PV 2.1, indicate the conductors entering the top side of gutter to comply with Section 312.6.A, "Deflection of Conductors" according to space for conductors for bending and terminations.(As per PV2.4.) 4. Sheets PV2.5 and PV2.6, no mention is made of the type of fixture , mounting or location of new WPLED lighting. 5. Sheet PV2.2 the conductors from the inverters to PV Panels are reversed, ones going to 75KW inverter to go to 100KW inverter. Ray T Majuta Elect Plan Review PDSD, C of Tucson 2/8/2013 Ray.Majuta@tucsonaz.gov |