Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T13CM01563
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 6 (DEVELOPMENT PLAN): THIS SHEET INDICATES A 36' WIDE STRUCTURE. DO WE HAVE BACK-TO-BACK STRUCTURES (CALCULATIONS INDICATE AN 18' WIDE STRUCTURE)? VERIFY. 2. PREVIOUS COMMENT 3: SHALL WE BASE THE VALUATION OF THIS PROJECT ON A 144' LENGTH? VERIFY. 3. STRUCTURAL CALCULATIONS; PAGE 5.6: WHERE IS THIS BOX BEAM USED ON THIS PROJECT? VERIFY. 4. SHEET S2; ISOMETRIC PLAN: AT THE BEAM TO COLUMN CONNECTION, A REFERENCE IS MADE TO DETAIL C. PROVIDE THAT DETAIL. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/10/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |