Permit Number: T13CM01563
Parcel: 99999999A

Address:
1000 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM01563
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1; GENERAL STRUCTURAL NOTES: THIS PROJECT REQUIRES THE 2012 IBC TO BE USED. THE CITY OF TUCSON HAS AN AMENDMENT (SECTION 1609.5.1.1) CONCERNING UPLIFT DUE TO MICROBURSTS. VERIFY THAT REQUIREMENT IS MET.
2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS.
3. SHEET S1; ISOMETRIC PLAN: PROVIDE THE DIMENSIONAL LENGTH OF THE CANOPY ('LENGTH VARIES' DOES NOT PROVIDE THE SQUARE FOOTAGE REQUIRED FOR PERMITTING).
4. SHEET S1; ISOMETRIC PLAN: PROVIDE THE HEIGHT OF THE CANOPY ('7'-0" MIN/10'-6" MAX' IS NOT ACCEPTABLE.
5. SHEET S1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/19/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/19/2013 JASON GREEN ENGINEERING REVIEW Approved
03/19/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/19/2013 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2013 CPIERCE1 OUT TO CUSTOMER Completed