Permit Number: T13CM01494
Parcel: 13339283A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T13CM01494
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2013 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied The decision letter for the special exception must be submittted with the plan set as a condition of approval.
03/18/2013 MICHAEL ST. PAUL ZONING REVIEW Denied The decision letter for the special exception must be submittted with the plan set as a condition of approval.
03/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T-1; BUILDING CODE AND STANDARDS: THE CURRENT ELECTRICAL CODE IS THE 2011 NEC, AND THE CURRENT BUILDING CODE IS THE 2012 IBC. REVISE.
2. STRUCTURAL CALCULATIONS; PAGE 1 (ANALYSIS): THE CODE LISTED IS THE 2006 IBC. THE CURRENT BUILDING CODE IS THE 2012 IBC, WITH CITY OF TUCSON AMENDMENTS (SECTION 1609.5.1.1 CONCERNING UPLIFT DUE TO MICROBURSTS). VERIFY THESE CODE REQUIREMENTS ARE MET IN THIS DESIGN.
3. GENERAL: ENSURE THE PLANS MEET THE REQUIREMENTS OF THE NEW CODES LISTED.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/25/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01494

1. The existing and current Panel Schedules are the same, not shown is the new 100 A circuit breaker now feeding the new BTS Cabinet per the new circuit with 3 #1 awg $8 grd in 2" conduit. The loads do not reflect the new circuit?

Ray Majuta
Elect Plan Review
DSD, Tucson
3/25/2013
Ray.Majuta@tucsonaz.gov
04/15/2013 CPIERCE1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed