Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T13CM01494
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2013 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | The decision letter for the special exception must be submittted with the plan set as a condition of approval. |
| 03/18/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | The decision letter for the special exception must be submittted with the plan set as a condition of approval. |
| 03/19/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T-1; BUILDING CODE AND STANDARDS: THE CURRENT ELECTRICAL CODE IS THE 2011 NEC, AND THE CURRENT BUILDING CODE IS THE 2012 IBC. REVISE. 2. STRUCTURAL CALCULATIONS; PAGE 1 (ANALYSIS): THE CODE LISTED IS THE 2006 IBC. THE CURRENT BUILDING CODE IS THE 2012 IBC, WITH CITY OF TUCSON AMENDMENTS (SECTION 1609.5.1.1 CONCERNING UPLIFT DUE TO MICROBURSTS). VERIFY THESE CODE REQUIREMENTS ARE MET IN THIS DESIGN. 3. GENERAL: ENSURE THE PLANS MEET THE REQUIREMENTS OF THE NEW CODES LISTED. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/25/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM01494 1. The existing and current Panel Schedules are the same, not shown is the new 100 A circuit breaker now feeding the new BTS Cabinet per the new circuit with 3 #1 awg $8 grd in 2" conduit. The loads do not reflect the new circuit? Ray Majuta Elect Plan Review DSD, Tucson 3/25/2013 Ray.Majuta@tucsonaz.gov |
| 04/15/2013 | CPIERCE1 | COMMUNICATIONS | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |