Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T13CM01492
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2013 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | The decision letter for the special exception must be submittted with the plan set as a condition of approval. |
| 03/18/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | The decision letter for the special exception must be submittted with the plan set as a condition of approval. |
| 03/19/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T-1; CODE COMPLIANCE: REMOVE THE IRC FROM THIS LIST. 2. SHEET T-1; CODE COMPLIANCE: THE IBC, IPC, AND IMC CURRENTLY USED ARE THE 2012 EDITION. REVISE. 3. SHEET T-1; CODE COMPLIANCE: THE ELECTRICAL CODE CURRENTLY USED IS THE 2011 EDITION OF THE NEC. REVISE. 4. GENERAL: ENSURE THE PLANS MEET THE REQUIREMENTS OF THE NEW CODES LISTED. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 04/15/2013 | CPIERCE1 | COMMUNICATIONS | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |