Review Details: CELL TOWER/ANTENNAS
Permit Number - T13CM01489
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2013 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | The decision letter for the special exception (SE-13-23) must be submittted with the plan set as a condition of approval. |
| 03/18/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | The decision letter for the special exception (SE-13-23) must be submittted with the plan set as a condition of approval. |
| 03/19/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T-1; BUILDING CODE AND STANDARDS: THE CURRENT ELECTRICAL CODE IS THE 2011 NEC, AND THE CURRENT BUILDING CODE IS THE 2012 IBC. REVISE. 2. STRUCTURAL CALCULATIONS; PAGE 1 (ANALYSIS): THE CODE LISTED IS THE 2006 IBC. THE CURRENT BUILDING CODE IS THE 2012 IBC, WITH CITY OF TUCSON AMENDMENTS (SECTION 1609.5.1.1 CONCERNING UPLIFT DUE TO MICROBURSTS). VERIFY THESE CODE REQUIREMENTS ARE MET IN THIS DESIGN. 3. GENERAL: ENSURE THE PLANS MEET THE REQUIREMENTS OF THE NEW CODES LISTED. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | |
| 04/15/2013 | CPIERCE1 | COMMUNICATIONS | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |